template-data/logo
sales@drainstore.com
installation@drainstore.com
consultancy@drainstore.com
accounts@drainstore.com
|||||||||||||||| ||

Conder ASP 25 Packaged Sewage Treatment Plant - 25 Population

Conder ASP 25 Packaged Sewage Treatment Plant - 25 Population
Description
Designed and tested in accordance with BSEN12566-3:2005 and with the British Water Code of Practice for Flows and Loads, the Clereflo ASP25 will serve a population of upto 25 persons and is suitable for residential and commercial projects where mains drainage is not available. Typical application include single dwellings, small communities or developments, refurbishments and rural barn conversions.

Specification

Hydraulic Load: 5000 (l/day)
Max Flow Per Day: 5.0 (M³)
Organic Load: 1500 (g BOD5/per day)
NH3: 200 (g per day)
Pipework Fitting: 110mm
Max Rated Power: 230 (Watts)
Estimated Power Consumption at Working Pressure: 190 (Watts)
Cover Size: 750 SQ
Plant Weight: 440kg

Dimensions...

A - O/A Diameter: 2080mm
B* - Standard Inlet Invert: 780mm
C - Inlet Invert to Base: 2370mm
D - Outlet Invert to Base: 2270mm
E* - O/A Depth: 3150mm

*Deeper inverts can be accommodated with extension shafts 

conder_asp_dimensions_1.jpg


Features and Benefits

  • Independently Tested to BSEN12566-3:2005
  • Completely below-ground installation
  • Easy to install for reduced costs
  • Proven technology with reliable performance
  • Quiet, odourless operation
  • Compact design with no moving parts
  • Typically up to 3 year desludging period
  • Deeper inverts available with a standard extension kit
  • Option for pumped influent or effluent
  • Effluent Standard: 20mg/l BOD; 30mg/l SS; 20mg/l NH3
  • Suitable for discharge to ground or watercourse (subject to Environment Agency consent)
Please note that should a neck extension be fitted to this tank, both the tank and the neck extension must be completely surrounded in concrete.

For further information, installation instructions and prices please Call 01773 767611                                  